Model: PT500-802
The minimum differential pressure is 100Pa;
3-5 times withstand voltage, suitable for dry gas differential pressure measurement;
High precision, stable, digital calibration adjustment, amplification integrated circuit;
Zero point, fullness, temperature compensation and linear compensation;
Aluminum alloy oxidation shell; 8mm + m10quick plug process connection;
Common keywords:
Micro differential pressure transmitter micro differential pressure sensor
Micro differential pressure transmitter
Chip:
The minimum differential pressure is 100Pa;
3-5 times withstand voltage, suitable for dry gas differential pressure measurement;
Zero point, fullness, temperature compensation and linear compensation;
High impedance, high precision and high stability;
More than 1 million times of service life;
Signal processing and output:
24 bit ADC sampling and processing chip;
DSP digital signal conditioning algorithm;
Multipoint linear temperature calibration;
Voltage and current overload protection;
Standard industrial signal output: 4-20mA (two-wire system), 0-20mA (three wire system), 0-5vdc, 0-10vdc, 0.5-4.5vdc (three wire system);
Digital communication signal output: rs485-rtu, ultra-low power rs485-rtu
Advanced 32 bit microprocessor and 24 bit ADC are adopted
The transmission protocol is MODBUS-RTU
Support baud rate: 1200 ~ 57600bps, check bits: none, odd, even
Support the user's secondary calibration, reset, anti reset, restore factory operations
Support 11 kinds of units switching, support floating point, integer, percentage, formatted output
The acquisition interval of 0 ~ 43200 seconds (12 hours) can be set, which can not only meet the needs of high-speed acquisition, but also trigger acquisition once to
minimize power consumption
Digital communication signal output: CAN2.0B
Measurement rate: 10... 1000Hz can be set, the default is 50 Hz
CANopen output built-in complete CANopen protocol stack, in line with ds301, ds404 specifications, support LSS services, support bootloader online upgrade;
Support baud rate (kbps) 20 / 50 / 100 / 125 / 250 (default) / 500 / 800 / 1000; support features of NMT / heartbeat / SDO / PDO / LSS / bootloader; CANopen protocol
stack can be customized according to user requirements;
J1939 output has built-in J1939 protocol stack. PGN, SPN and name can be configured freely, and bootloader online upgrade is supported;
Support baud rate (kbps) 20 / 50 / 100 / 125 / 250 (default) / 500 / 800 / 1000; support free configuration of features such as PGN, SPN and name
The J1939 protocol stack can be customized according to the user's requirements;
Structure:
Aluminum alloy oxidation shell; 8mm + m10quick plug process connection;
Small structure, tight wire nut waterproof, electrical connection;
Supporting four / five core shielded cable;
Application:
Pressure measurement and monitoring of negative pressure, dust-free workshop, Department, etc;
Pressure measurement and monitoring of buildings, ventilation, etc;
Pressure measurement and monitoring of dust collection pipeline, waste gas treatment, etc;
Smart city
Fire fighting system
Natural gas pipeline
Air supply system
Gas supply system
Gas supply pipeline
Measuring medium: dry gas
Pressure form: differential pressure
Range:
0~100、200、300、500、1000(Pa);
0~1、2、3、5、10、20、30、40、50、70、100(KPa);
-100KPa~-10KPa~0~100(KPa);
±500Pa~±100KPa;
Static pressure (withstand voltage): 3 ~ 5 times of measuring range
Comprehensive accuracy: ± 0.25% FS; ± 0.5% FS; ± 1% FS
Nonlinearity: ≤ 0.5% FS
Repeatability: ≤ 0.25% FS
Output signal:
Current type: 4-20mA two-wire system; 4-20mA / 0-20mA three-wire system
Voltage type: 0 ~ 5VDC, 0 ~ 10VDC, 0.5 ~ 4.5vdc three wire system
Digital type: rs485-rtu, low power rs485-rtu
CAN2.0B (supports CANopen, J1939 Protocol)
Supply voltage:
24VDC(9~30VDC)
5VDC (0.5 ~ 4.5vdc output type)
3.1 ~ 6.1vdc (low power rs485-rtu)
Service life: ≥ 1 million times
Insulation impedance: ≥ 1000 m Ω / 100VDC
Load impedance: current output: ≤ 800 Ω; voltage output: ≥ 50K Ω
Medium temperature: - 20 ~ 70 ℃/
Ambient temperature: - 20 ~ 70 ℃
Compensation temperature: 0 ~ 60 ℃
Response time: ≤ 3MS
Overload pressure: 150% FS
Failure pressure: 3 times of measuring range (less than 40MPa); 2 times of measuring range (measuring range greater than 41mpa)
Electrical connection: Waterproof tight wire nut directly leads out, can be matched with explosion-proof electrical connection
Protection grade: IP65 / IP68
Connecting cable: tightening nut, standard length: 3M
Connection material: aluminum alloy
Process connection: φ 8 quick plug + M10 thread (Universal) Specification can be made by users